The integrated kiosk substation is the optimal technical solution for customers with requirements for saving construction area and high aesthetics.
Integrated kiosk substation is used in loop medium voltage grids, with voltage up to 36kV, rated current up to 630A.
Low voltage switchgear, RMU (Ring main unit) are imported from leading manufacturers such as Schneider, ABB, Siemens, LS ... so the integrated kiosk station has high quality, reliability and can meet the special requirements of the customers. With its special design, the kiosk can be easily transported, installed and operated.
Technical specifications
High-voltage compartment
• Applicable standards: IEC 60694
• Rated voltage: 12/24 / 36kV
• Typical configuration: Typical configuration: 03-compartment RMU 24kV 630A circuit board, 02 to / in, one to the transformer. Protect the transformer with a HRC fuse
Transformer compartment
• Applicable standards: IEC 60076
• Rated voltage on the high side: up to 35kV
• Rated voltage on the low-voltage side: 690V
• Rated frequency: 50Hz
• Transformer capacity: up to 2000kVA
Low-voltage compartment
• Applicable standards: IEC 60439-1
• Rated voltage: 690V
• Rated current: up to 3200A
• Typical configuration includes: prevent loss (clock, transformer, indicator), prevent switch (ACB or total MCCB, branch MCCB, lightning valve).